2.6 RECLOSER ELEMENT
AR FUNCTION:
AR MAX SHOTS:
2
AR DEAD TIME 1 ... 4:
AR RESET LO DELAY:
AR INCOM. SEQ TIME:
AR RST TIME:
Autoreclose initiation masks:
st
nd
rd
After 1
, 2
, 3
2-12
the recloser may operate only if it is ENABLED. If DISABLED the recloser will be Out of
Service.
specifies the number of reclosures that can be attempted before recloser goes to
LOCKOUT status, because the fault is permanent.
these are the intentional delays before first, second, third and fourth breaker automatic
reclosures.
this setting establishes how long the breaker should stay closed after a manual close
command, in order for the autorecloser to reset from LOCKOUT.
this timer is used to set the maximum time interval allowed for a single reclose shot. It is
started whenever a reclosure is initiated and is active when the scheme is in the
RECLOSE IN PROGRESS state. If all conditions allowing a breaker closure are not
satisfied when this time expires, the scheme goes to LOCKOUT.
a reset timer output resets the recloser following a successful reclosure sequence. The
setting is based on the breaker "reclaim time" which is the minimum time required
between successive reclose sequences.
used to select which events will initiate the autorecloser scheme.
th
trip masks: used to select which function will be enabled to trip.
, 4
MIFII Digital Feeder Relay
2 PRODUCT DESCRIPTION

2.6.3 RECLOSER SETTINGS

GEK-106237P