GE MIFII GEK-106237P Instruction Manual page 226

Digital feeder protection with recloser
Table of Contents

Advertisement

APPENDIX E
APPENDIX E OPTION C MODELSE.1INTRODUCTION
This appendix describes the main features implemented in MIFII relays with protocol option C:
IEC 60870-5-103 communication protocol added
Two independent communication ports
The general settings of these models are described in the following table:
ENERVISTA MII SETUP
PRODUCT SETUP
PRODUCT SETUP
Relay Status
Relay Operation
Frequency
Frequency
ModBus Format
---
Phase CT ratio
Phase CT Ratio
Ground CT ratio
Ground CT Ratio
HMI Password
---
Comm Password
---
Slave Address
---
Communication Baud rate ---
Communication 2 Baud
---
rate
Prefault cycles
Prefault Cycles
GEK-106237P
HMI
DEFAULT
PRODUCT SETUP
Relay Operation
DISABLE
Frequency
60 Hz
ModBus Format
Intel
Phase CT Ratio
1
Ground CT Ratio
1
HMI Password
1
Comm Password
1
Slave Address
1
Comm Baud Rate
9.6
COM2 Baud rate
9.6
Prefault Cycles
50
MIFII Digital Feeder Relay
E.1 INTRODUCTION
RANGE
STEP
READY / DISABLE
NA
50/60 Hz
NA
Intel/Motorola
NA
1-4000
1
1-4000
1
1-9999
1
1 – 255
1
1 – 255
1
0.3, 0.6, 1.2, 2.4, 4.8,
NA
9.6, 19.2
0.3, 0.6, 1.2, 2.4, 4.8,
NA
9.6, 19.2
10-140
1
E-1