4 COMMUNICATIONS

4.3 SETPOINT

4.3SETPOINT
Clicking on the Setpoint menu entry gives access to Settings, Configuration, Logic Configuration and Clock.

4.3.1 SETTINGS

The Settings sub-menu is the same for all MII family relays, and shows all relay settings divided in two groups: Main
Settings and Advanced Settings. The first settings group has basic settings (main protection functions). The second
settings group includes more advanced settings (double settings group, customized curves, etc.), needed only if more
complex protection schemes are required
The purpose of this division is to simplify the use of the relay for those users only requiring the basic functionality of the
relay.
4
Figure 4–7: SETTINGS MENU
Once in the corresponding sub-menu, either Main Settings or Advanced Settings, the procedure to enter and modify any
setting value is the same:
Select the settings group (the function selected in the example is the51P function in a MIFII).
Edit the setting double-clicking on the value (for example, 51Penable).
Modify the value of the setting (see Figure 4–9: to Figure 4–11:).
Confirm/Accept the modified value.
Store the settings in the relay (if working in Emulation mode, this option stores them on a temporay file that must be saved
with the File->Save option in order to preserve them) with the Store button. If the OK button is pressed without having
pressed Store (a window asking confirmation will appear), the settings of this group will be discarded.
Figure 4–8: FUNCTION MENU
GEK-106237P
MIFII Digital Feeder Relay
4-7