13 TROUBLESHOOTING GUIDE
13 TROUBLESHOOTING GUIDE 13.1MIFII TROUBLESHOOTING GUIDE
MIFII units have been designed and verified using the most advanced and reliable equipment. Mounting and testing
automation ensure a high consistency of the final product. Before sending a unit back to the factory, we strongly
recommend you follow the recommendations below.
Even if it will not always solve the problem, at least they will help define it better for a quicker repair.
If you need to send a unit back to the factory for repair, please use the appropriate RETURN MATERIAL AUTHORIZATION
process, and follow the shipping instructions provided by our Service Department, especially in the case of international
shipments. This will lead to a faster and efficient solution of your problem.
CATEGORY
SYMPTOM
The relay does not trip
PROTECTION
When feeding the unit, no
indicator is light up
GENERAL
The relay does not
communicate via the front
RS232 port
COMMUNICATIONS
The relay does not
communicate via the
RS485 port
GEK-106237P
POSSIBLE CAUSE
- Element not enabled
- Output not assigned
- Inappropriate setting group
- Insufficient power supply
- Fused fuse
- Loose fuse
- Incorrect wiring
- Incorrect cable
- Damaged cable
- Relay or PC not grounded
- Incorrect baud rate, port, address,
etc.
- Relay or PC not grounded
- Incorrect polarity
- Incorrect baud rate, address, etc.
MIFII Digital Feeder Relay
13.1 MIFII TROUBLESHOOTING GUIDE
RECOMMENDED ACTION
-Set the element permission to ENABLE
-Program the output to the desired element
using ENERVISTA MII SETUP-SETPOINT-
RELAY CONFIGURATION
- Make sure that desired group is active
(group 1 or group 2) and/or that there is no
settings group change input that could
modify the active group
- Verify the voltage level using a multimeter
in the power supply terminals, and check
that it is within the model range.
- Remove the power supply board and
replace the fuse.
- Make sure you are using a straight cable.
- Replace the cable
- Ensure ground connection
- Make sure that the communication
parameters in the computer match the
ones in the relay.
- Ensure ground connection
- Invert polarity
- Test other baud rate, etc.
13