Phase / Ground Toc Settings (51P/ 51G) (Group 2); Phase / Ground Ioc Settings (50P1/ 50P2/ 50G1/ 50G2) (Group 2) - GE MIFII GEK-106237P Instruction Manual

Digital feeder protection with recloser
Table of Contents

Advertisement

5.3 ADVANCED SETTINGS
Ph TOC Funct.
group 2
51P Permission to
Trip
51P Pickup Value
51P Curve Type
51P Time Dial
51P Definite Time
Delay
Gnd TOC Fun.
group 2
51G Permission to
Trip
51G Pickup Value
(1/5 A ground)
51G Pickup Value
(sensitive ground)
51G Curve Type
5
51G Time Dial
51G Definite Time
Delay
Ph IOC High Set group 2
50P1 Permission to Trip
50P1 Pickup
50P1 Time Delay
Ph IOC Low Set group 2
50P2 Permission to Trip
50P2 Pickup
50P2 Time Delay
Gnd IOC High Set group 2
50G1 Permission to Trip
50 G1 Pickup (1/5 A ground)
50 G1 Pickup Value (sensitive
ground)
50 G1 Time Delay
Gnd IOC Low Set group 2
50G2 Permission to Trip
50G2 Pickup (1/5 A ground)
50G2 Pickup Value (sensitive
ground)
50G2 Time Delay
5-8
ENERVISTA MII
HMI
SETUP
Phase TOC 51P
PHASE TOC 51P
(group 2)
Trip Enable 51P
Trip Enable 51P
Pickup 51P
Pickup 51P
Curve 51P
Curve 51P
TD mult 51P
TD mult 51P
Def Time 51P
Def Time 51P
Ground TOC 51G
GROUND TOC 51G
(group 2)
Trip Enable 51G
Trip Enable 51G
Pickup 51G
Pickup 51G
Pickup 51G
Pickup 51G
Curve 51G
Curve 51G
TD mult 51G
TD mult 51G
Def Time 51G
Def Time 51G

5.3.2 PHASE / GROUND IOC SETTINGS (50P1/ 50P2/ 50G1/ 50G2) (GROUP 2) (

ENERVISTA MII SETUP
PHASE IOC 50P1 (group 2)
Trip Enable 50P1
Pickup 50P1
Delay 50P1
PHASE IOC 50P2 (group 2)
Trip Enable 50P2
Pickup 50P2
Delay 50P2
GROUND IOC 50G1 (group 2) Ground IOC 50G1
Trip Enable 50 G1
Pickup 50G1
Pickup 50G1
Delay 50G1
GROUND IOC 50G2 (group 2) Ground IOC 50G2
Trip Enable 50G2
Pickup 50G2
Pickup 50G2
Delay 50G2
MIFII Digital Feeder Relay

5.3.1 PHASE / GROUND TOC SETTINGS (51P/ 51G) (GROUP 2)

DEFAULT
RANGE
No
Yes/No
0.5 In (Phase) 0.1 – 2.4 In (Ph)
DEFINITE
DEFINITE TIME, USER, MOD INVERSE,
TIME
VERY INVERSE, EXTR INVERSE,
INVERSE LONG, INVERSE SHORT
0.5
0.05 – 2.00
5
0.5 – 20.0
0.5
0.5 – 10.0
1.00 s.
0.00 – 600.00 s.
No
Yes/No
0.5 In
0.10 – 2.40 In (Gnd)
(Ground)
0.005 A
0.005-0.12 A
DEFINITE
DEFINITE TIME, USER, MOD INVERSE,
TIME
VERY INVERSE, EXTR INVERSE,
INVERSE LONG, INVERSE SHORT
0.5
0.05 – 2.00
5
0.5 – 20.0
0.5
0.5 – 10.0
1.00
0.00 – 600.00 s
HMI
DEFAULT
Phase IOC 50P1
Trip Enable 50P1
No
Pickup 50P1
1 In (Phase)
Delay 50P1
0 s.
Phase IOC 50P2
Trip Enable 50P2
No
Pickup 50P2
1 In (Phase)
Delay 50P2
0 s.
Trip Enable 50 G1 No
Pickup 50G1
1 In (Ground)
Pickup 50G1
0.005 A
Delay 50G1
0 s.
Trip Enable 50G2
No
Pickup 50G2
1 In (Ground)
Pickup 50G2
0.005 A
Delay 50G2
0 s.
5 SETTINGS
STEP
NA
0.01 In
(P)
NA
(IEC curves)
0.01
(ANSI curves)
0.01
(IAC curves)
0.01
1.00 s.
NA
0.01 In
(G)
0.001 A
NA
(IEC curves)
0.01
(ANSI curves)
0.01
(IAC curves)
0.01
0.01 s
RANGE
STEP
Yes/No
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0.00 –600.00s.
0.01 s.
Yes/No
NA
0.1 – 30 In (Ph)
0.1 In (Ph)
0.00 –600.00s.
0.01 s.
Yes/No
NA
0.1 – 30 In (Gnd) 0.1 In (G)
0.005-0.12 A
0.001 A
0.00 – 600.00 s.
0.01 s.
Yes/No
NA
0.1 – 30 In (Gnd) 0.1 In (G)
0.005-0.12 A
0.001 A
0.00 –600.00s.
0.01 s.
GEK-106237P