APPENDIX C
C.3COMMAND EXECUTION
®
Commands with ModBus
Intel format setting are executed in two steps: selection and confirmation. First, send the
command or operation selection command. When the relay response arrives, send the confirmation. It is necessary to send
the relay password. The structure for both commands is the same; the only variation is the related code.
When Motorola is the selected ModBus format setting, commands only need the confirmation step.
®
The ModBus
function used is 16 (10h), PRESET MULTIPLE SETPOINTS. It consists of a writing of the operation code in
address 0 (000H). The available commands list is as follows:
INTEL SELECTION
Intel Request:
FIELD
Relay address
Function
Beginning address
Number of registers
Number of bytes
Value of the registers Register1=> (INTEL) Command code (Low byte – High byte)
CRC
Intel Reply:
GEK-106237P
INTEL
COMMAND
SELECTION CONFIRMATION CONFIRMATION
Setting change
01H
Thermal Image
03H
Reset
Open breaker
07H
LEDs reset
09H
Change to group 1
0DH
Change to group 2
0FH
Oscillography trigger 17H
Set number of
2FH
openings
Set I2
31H
Close breaker
39H
Time synchronization 0FEH
LENGTH
1 byte
1 byte (10H)
1 word (000H) (High byte – low byte)
1 word (0001H) (High byte – low byte)
1 byte (02H)
1 word
FIELD
LENGTH
Relay address
1 byte
Function
1 byte (10H)
Beginning address 1 word (000H) (High byte – low byte)
Nº of registers
1 word (0003H) (High byte – low byte)
CRC
1 word
MIFII Digital Feeder Relay
MOTOROLA
02H
02H
04H
04H
08H
08H
0AH
0AH
0EH
0EH
10H
10H
18H
18H
30H
30H
32H
32H
3AH
3AH
Not applicable
0FEH
C.3 COMMAND EXECUTION
C
C-3