9 RELAY COMMISSIONING

9.13 MODEL E: GROUND IOC HIGH SETTING ELEMENT (50G1)

9.13MODEL E: GROUND IOC HIGH SETTING ELEMENT (50G1)
Enable only 50G1 element.
Set time delay as needed. If the time delay is set to 0 sec., the relay operating time will be between 10 to 50 ms. Also, the
customer has to test pickup.
With 0.9 times the pickup current the relay should not trip.
With 1.1 times the pickup current the relay should trip in between 10 to 50 ms.
With 4 times the pickup current the relay should trip in between 10 to 40 ms.
9
GEK-106237P
MIFII Digital Feeder Relay
9-13