APPENDIX F
F.5 CONCLUSIONS
F.5CONCLUSIONS
The GE MIFII Relay works according to its specifications and to the IEC Standard as well.
In the real case used for this report, the specification would be the following range:
Lower time limit ≤ Time to trip ≤ Upper time limit
30.375 ≤ 50.1 ≤ 70.875
IEC Standard does not specify timing accuracy for pickup values lower than 2Gs; therefore, the manufacturer's specified
accuracy must be applied.