2 PRODUCT DESCRIPTION
2.11 OSCILLOGRAPHY (AVAILABLE IN OPTION 1 AND OPTION 2 MODELS)
In the ADVANCED SETTINGS group, there is a sub-group called OSCILLOGRAPHY MASKS, from where the above-
mentioned causes can be masked. They are detailed in the SETPOINT – SETPOINT – ADVANCED SETTINGS –
OSCILOGRAPHY MASK section.
MIFII relay with option C stores 4 oscillography records, with a resolution of 16 samples per cycle with a total length of
150 cycles (including prefault cycles) each register. In General Settings there is a setting for prefault cycles. It is
adjustable from 10 to 140 cycles.
2
GEK-106237P
MIFII Digital Feeder Relay
2-19