2 SYSTEM CONFIGURATION
2.4.9 SSCNET
cables and connection method
Attach a cap to connectors
of system not being used.
This section describes how to connect between the Motion CPU module and servo
amplifiers.
Between the Motion CPU module and servo amplifiers is connected by SSCNET
cable. When using the Q172HCPU, only 1 SSCNET cable for connection to servo
amplifier can be used. (Connect to CN1.) When using the Q173HCPU, up to 2
SSCNET cables for connection to servo amplifier can be used. (Connect to CN1 and
CN2.)
Up to 16 servo amplifies can be connected to 1 SSCNET cable.
(However, when using the Q172HCPU, up to 8 servo amplifiers can be connected.)
(1) Connection between the Q173HCPU and servo amplifiers
Q173HCPU
Motion CPU module
CN2
CN1
SSCNET
1)
CN1A
CN1B
Servo amplifier
SSCNET
1)
CN1A
CN1B
Servo amplifier
(Note): It cannot communicate with that the connection of
CN1A and CN1B is mistaken.
2 - 74
SSCNET
cable length
MR-J3BUS M use
1) 3m(9.84ft.)
MR-J3BUS M-A use
1) 20m(65.62ft.)
MR-J3BUS M-B use
1) 50m(164.04ft.)
SYSTEM1
CN1A
1)
CN1B
Servo amplifier
SYSTEM2
CN1A
1)
CN1B
Servo amplifier
Cap
Cap