D Ia G N O S Is; Refrigerant System - Chevrolet 1977 light duty truck Service Manual

Table of Contents

Advertisement

REFRIGERANT SYSTEM

The
following is a description o f the type o f
sym ptom each refrig eran t com ponent will evidence if a
defect occurs:
CO M PRESSO R
A compressor defect will ap p e a r in one o f four
ways: Noise, seizure, leakage, or low discharge pressure.
N O T E : R esonant com pressor noises are not cause
for alarm ; however, irregular noise or rattles m ay
indicate broken parts or excessive clearances due to
wear. To check seizure, de-energize the magnetic
clutch and check to see if drive plate can be
rotated. If rotation is impossible, compressor is
seized (See "False C om pressor Seizure"). To check
for a leak, refer to leak testing in the service
m anual. Low discharge pressure m ay be due to a
faulty
internal
seal o f
restriction in the compressor.
Low discharge pressure m ay also be due to an
insufficient
refrigerant
elsewhere in the system. These possibilities should
be checked prior to servicing the compressor. If the
compressor is inoperative, but is not seized, check
to see if current is being supplied to the magnetic
clutch coil terminals.
CO NDENSER
A condenser may be defective in two ways: it may
leak, or it may be restricted. A condenser restriction will
result in excessive compressor discharge pressure. If a
partial restriction is present, sometimes ice or frost will
form im m ediately after the restriction as the refrigerant
expands after passing through the restriction. If air flow
through the condenser or rad ia to r is blocked, high
discharge pressures will result. D uring norm al condenser
operation, the outlet pipe will be slightly cooler than the
inlet pipe.
RECEIVER-DEHYD RATO R
A defective receiver-dehydrator may be due to a
restriction inside the body o f the unit. A restriction at
the inlet to the receiver-dehydrator will cause high head
pressures. Outlet tube restrictions will be indicated by
low
head
pressures
and
excessively
cold
receiver-dehydrator
indicative o f a restriction.
E X P A N S IO N VALVE
A m alfunction o f the expansion valve will be caused
by one o f the following conditions: valve stuck open,
valve stuck closed, broken power element, a restricted
screen o r an im properly located or installed power
elem ent bult. The first three conditions require valve
DIAGNOSSS
the compressor,
or
a
charge
or
a
restriction
little
or
no
cooling.
An
outlet
may
be
replacement. The last two may be corrected by replacing
the valve inlet screen and by properly installing the
power element bulb.
Attachment o f the expansion valve bulb to the
evaporator outlet line is very critical. The bulb must be
attached tightly to the line and must make good contact
with the line along the entire length of the bulb. A loose
bulb will result in high low side pressures and poor
cooling.
Indications o f expansion valve trouble are provided
by Perform ance Tests; consult Diagnostic Charts.
VALVE STU CK OPEN
NOISY COM PRESSOR.
N o Cooling - Freeze Up.
VALVE STUCK CLOSED, BROKEN POW ER
E L E M E N T OR P L U G G E D SCREEN
Very Low Suction Pressure.
N o Cooling.
PO ORLY LOCA TED POW ER E L E M E N T BULB
N orm al Pressure.
Poor Cooling.
Diagnosis for Defective Valve
The
following
procedure
determine
if a malfunction
expansion valve.
1.
Check to determ ine if the system will meet the
perform ance test as outlined previously. If the expansion
valve is defective, the low pressure readings (evaporator
pressure) will be above specifications.
2.
The loss o f system perform ance is not as evident
when the compressor head pressure is below 200 psi.
Therefore, it m ay be necessary to increase the system
head pressure
by partially blocking
Disconnect
the
blower
"perform ance check" to determ ine if the evaporator
pressure can be obtained.
3.
The system will also indicate a low refrigerant
charge by bubbles occurring in the sight glass.
EVAPO RATOR
W hen the evaporator is defective, the trouble will
show up as an inadequate supply o f cool air. A partially
plugged core due to dirt, a cracked case, or a leaking seal
will generally be the cause.
REFR IG ER A N T LINE R E S TR IC T IO N S
Restrictions in the refrigerant lines will be indicated
as follows:
1.
Suction Line - A restricted suction line will
cause low suction pressure
discharge pressure and iittle or no cooling.
2.
Discharge Line - A restriction in the discharge
line generally will cause the pressure relief valve to open.
3.
Liquid Line - A liquid line restriction will be
must
be
followed
is due
to a defective
the condenser.
lead
wire
and
repeat
the
at the compressor,
low
to

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1979 light duty truck

Table of Contents