Function – [Communication Timing]
Function
[Communication Timing]
Description
Defines the network communication start timing at the powering of the LM ADAPTER.
Using CP
【nciSet_1】
Control unit
LM ADAPTER
Relating CP
【nciStartHrtBt】 【nciStartOutTm】 【nciInitStartTm】
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Nothing
To be used for setting of the timing to start the operation of Neuron Chip after completing the initialization. While
Purpose
the Neuron Chip is stopped during the initialization setting of LM ADAPTER with air conditioners.
Outline of
At the set time after powering, the operation of Neuron Chip will start enabling the LonWorks communication of
operation
LM ADAPTER.
Communication Image
① [initialize]
②[setting time]
Related configuration property
- Send Start Time 【nciStartOutTm】
- Send Heartbeat Start Time 【nciStartHrtBt】
- Initialize Start Time【nciInitStartTm】
Caution
- This does not represent the start timing of the output at changing (event output). Setting is required by the configuration property
(Send Start Time 【nciStartOutTm】) additionally.
BMS
Power Recovery
NC will not reply
BMS
Power Recovery
NC will not reply
69
LM-AP
Poll demand
Initialization setting of LM ADAPTER
Poll demand
response
LM-AP
Poll demand
Initialization setting of LM ADAPTER
Poll demand
Poll demand
response
LMAP03U