Function – [Collective ON/OFF]
Function
[Collective On/Off State]
Description
Monitoring the operation status of all units controlled by LM ADAPTER collectively.
Using NV
【nvoAllOnOff】
Control unit
All of indoor units controlled by LM ADAPTER
Outline of
The "Run" will be output even if 1 set of indoor units or ventilation units being controlled by LM ADAPTER is
operation
operating.
The "Stop" will be output at the stopping of all units.
Communication Image
① Operation from BMS
Restrictions
- State output of ventilation unit interlocked with indoor unit
When operating only the ventilation unit interlocked with indoor unit by using the local remote controller, "Collective stopping" will be
output to the Building management system unless other indoor unit or individually operating ventilation unit is not being operated.
BMS
[Run] operation
state [Run]
state [Stop]
40
LM-AP
[Run] operation
state [Run]
state [Stop]
LMAP03U
IC
② Operation from local
remote controller