Function – [Send Start Time]
Function
[Send Start Time]
Description
Defines the start time of the output network variable change at powering of LM ADAPTER.
Using CP
【nciStartOutTm】
Control unit
LM ADAPTER
Relating CP
Nothing
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Nothing
This is to set the start time of output at changing when LM ADAPTER is powered. When the plural LM
ADAPTERS are installed, the concentration of the output at changing can be prevented.
Purpose
In the case using the initial output to match the image, this can further be applied to delay the automatic
updating to avoid excess output during the initial outputting.
Outline of
The output at changing will be effective when the set time is passed after powering. The status change within the
operation
set time will be applied with the output at changing when passing the set time.
Communication Image
①Status change within the set time
②Status change when passing the set time
Cautions
- After initializing LM ADAPTER, the request before the starting of the output at changing will be valid, but the state change will not be
provided.
- Only the bound variables are output.
BMS
Power Recovery
IC_01[Stop]
IC_01[Run]
56
LM-AP
IC_01[Run]
IC_01[Stop]
IC_01[Run]
LMAP03U
IC_01