Mitsubishi Electric LMAP03U Technical Manual page 57

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [ Minimum Send Time]
Function
[Minimum Send Time]
Description
Defines the minimum send time between the output network variables.
Using CP
【nciMinOutTm】
Control unit
LM ADAPTER
Relating CP
Nothing
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Variable output previously (in a unit of same indoor unit)
When a state change occurs continually, the variable will be output with a certain interval not to output all state
Purpose
changes.
When a state change occurs on the same unit that output previously, the output at changing will not be provided
Outline of
within the set time. It will be supplied after elapsing the set time.
operation
When the unit other than that output previously changes its state, it will be output even within the set time.
Communication Image
【nciMinOutTm】
①Same indoor unit state changing
【nciMinOutTm】
②Different indoor unit state changing
【nciMinOutTm】
Cautions
- Effective for the output interval between the output variables on a same indoor unit.
- Unable to keep the output interval between different indoor units.
- Only the bound variables are output.
BMS
IC_01[Run]
IC_01[Stop]
IC_01[Cool]
IC_02[Run]
IC_01[Run]
54
LM-AP
IC_01[Run]
IC_01[Stop]
IC_01[Fan]
IC_01[Cool]
IC_02[Run]
IC_01[Run]
LMAP03U
IC_01
IC_02