Function – [Thermostat ON/OFF state]
Function
[Thermo On/Off state_1] [Thermo On/Off_2]
Description
Monitoring the thermostat state of indoor units, run/stop state, and the state of auxiliary heater for heating.
Using NV
LMAP02-E:【nvoThermo_n】
LMAP03U:【nvoThermoSt_n】【nvoThermo_n】
Control unit
Indoor unit
Outline of
The thermostat status of each indoor unit is monitored. In the case of CITY MULTI, the compressor of the
operation
outdoor unit turns off if the thermostat of all indoor units within a same refrigerant system turn off. (It depends on
the operating condition.)
*While the thermostat is turned off forcibly, the thermostat OFF will be output. (LMAP03U only)
Communication Image
BMS
state [Thermostat ON]
state [Thermostat OFF]
LM-AP
state [Thermostat ON]
state [Thermostat OFF]
35
LMAP03U
IC
Thermostat [ON]
→ Thermostat [OFF]