Function – [Set Point]
Function
[Setpoint] [Setpoint State]
Description
Setting and monitoring the target temperature of indoor units.
Using NV
LMAP02-E: 【nviSetPoint_n】 【nvoSetPoint_n】
LMAP03U : 【nviSetP_n】 【nvoSetP_n】
Control unit
Indoor unit
Outline of
The target room temperature for each indoor unit is set and monitored.
operation
In accordance with the operation mode of indoor units, the temperature
range that can be set is different.
Set temperature unit: 1.0ºC
Communication Image
① Operation from BMS
Restrictions
- To set temperature from the Building management system, set so that it stays within the set temperature range above.
- The action by the setting out of the set temperature range differs depending on the operation mode at that time.
<At cooling/drying mode> Operated for 19ºC or less, or 31ºC or more - - - Set to 19ºC, 30ºC respectively
<At heating mode> Operated for 17ºC or less, or 29ºC or more - - - Set to 17ºC, 28ºC respectively
<At automatic mode> Operated for 19ºC or less, or 29ºC or more - - - Set to 19ºC, 28ºC respectively
BMS
[xx℃] setting
state [xx℃]
state [xx℃]
45
LM-AP
[xx℃] setting
state [xx℃]
state [xx℃]
LMAP03U
Mode
Setting Range
Auto
19 ~28 ℃
Cool
19 ~30 ℃
Heat
17 ~28 ℃
Dry
19 ~30 ℃
Fan
Not used
IC
② Operation from local
remote controller