Mitsubishi Electric LMAP03U Technical Manual page 68

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Space Temperature Setting]
Function
[Monitoring Time]
Description
Defines the indoor temperature monitor interval from the LM ADAPTER to the indoor unit.
Using CP
【nciAnlgMonTm】
Control unit
LM ADAPTER
Relating CP
【nciSndHrtBt_2】
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Nothing
Purpose
To be used to modify the monitoring interval of room temperature
Outline of
With the set interval, room temperature is monitored for indoor units from LM ADAPTER.
operation
Depending on the connecting number of indoor units, the monitor interval that can be set is different.
Function
[Spacetemp Width]
Description
Defines the minimum variation width of the output when 【nvoSpaceTemp_n】(Space Temperature) changes.
Using CP
【nciAnalogWidth】
Control unit
LM ADAPTER
Relating CP
【nciSndHrtBt_2】
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Nothing
Purpose
To be used for suppressing frequent outputs at the changes of room temperature
The output at changes will be provided if the status change of room temperature becomes more than the set
Outline of
temperature range. The output at changes will not be provided if the status change of room temperature
operation
becomes less than the set temperature range.
Changing range: 0.5 ℃~2.0 ℃, Temperature unit: 0.5 ℃
Communication Image
Restriction
- The set range differs depending on the connecting number of indoor units.
Caution
- To set a periodical monitor interval below 10 minutes, it is required to change SW1-3 on LM ADAPTER to ON. Please make the
connecting numbers 30 sets or less.
BMS
65
LM-AP
Monitoring
[Room Temperature]
Response
Monitoring
[Room Temperature]
Response
Monitoring
[Room Temperature]
Response
LMAP03U
IC_01
【nciAnlgMonTm】
【nciAnlgMonTm】
【nciAnlgMonTm】