Mitsubishi Electric LMAP03U Technical Manual page 55

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Group Number]
Function
[Group Number]
Description
Outputting group information on the indoor unit or ventilation unit.
Using NV
【nvoGroup_n】
Control unit
Indoor unit
Outline of
The group information (No.) of indoor unit or individually operating ventilation unit (not locked with indoor unit)
operation
will be output. As this variable is not applied with the event output, acquire the data by Poll or Fetch demand.
The group information will only be set when grouping is performed with other system controller.
Communication
① Polling or Fetching from BMS
Restrictions
- About output at changing
This variable is of universal and not applicable to the output at changing. Use the Poll or Fetch demand for acquisition as shown
above.
- Condition to output indoor unit group information
The group information will be output only when using other system controller like the centralized controller together in combination.
BMS
Poll demand
output [Group Number]
52
LM-AP
LMAP03U
IC

Advertisement

Table of Contents
loading

Table of Contents