Mitsubishi Electric LMAP03U Technical Manual page 63

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Recerive Heartbeat]
Function
[Receive Heartbeat_1] [Receive Heartbeat_2]
Description
Defines the maximum elapse time from the last update of the network variables.
Using CP
【nciRcvHrtBt_1】 【nciRcbHrtBt_2】
Control unit
LM ADAPTER
Relating CP
Nothing
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Objective variable lastly updated
This is to be used to determine the operation when the periodical updating to LM ADAPTER is eliminated such
Purpose
as in the case when the master system is downed or communication error
is occurred.
When the set time is passed after updating the network variable lastly (by renewing the set value for the input
Outline of
network variable, and the poll/fetch demanding for the output network variable), the setting will automatically be
operation
cancelled.
To continue the set state, update one of the variables of the objective unit (address) periodically.
Communication Image (In the case of local prohibit)
①Update within the set time
②Monitor within the set
③No update and monitor
within the set time
BMS
IC_01[Prohibit ON/OFF]
IC_01[Prohibit ON/OFF]
IC_01 Poll demand
IC_01[Prohibit ON/OFF]
IC_01[Permit ON/OFF]
60
LM-AP
IC_01[Prohibit ON/OFF]
IC_01[Prohibit ON/OFF]
IC_01[Permit ON/OFF]
IC_01[Permit ON/OFF]
LMAP03U
IC_01