Mitsubishi Electric LMAP03U Technical Manual page 53

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Collective Alarm for LM ADAPTER]
Function
[Collective Alarm for LM ADAPTER]
Description
Monitoring collectively the communication state of indoor units controlled by LM ADAPTER
Using NV
【nvoAllAlarmLMAP】
Control unit
All of indoor units controlled by LM ADAPTER
Outline of
Alarm will be output if communication error occurs between the indoor unit and ventilation unit being controlled
operation
with LM ADAPTER even on the one set.
Error will be detected when the communication is interrupted for a certain time (about 50 ~ 60 minutes).
When all communication errors are restored, the error will be restored as a result.
Communication
Under communication
abnormal detection
(about 50 – 60 minutes)
Cautions
- Even under a communication error occurred, the request input to and the state output from LM ADAPTER are possible.
- Depending on the cause generating communication error, air conditioners may be operated from the local remote controller.
BMS
state [Alarm]
50
LM-AP
Error
occurred
LMAP03U
IC