Mitsubishi Electric LMAP03U Technical Manual page 47

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Space Temperature]
Function
[Space Temperature State]
Description
The room temperature designed to be measured by the indoor unit will be measured.
Using NV
【nvoSpaceTemp_n】
Control unit
Indoor unit
Outline of
The room temperature (or inlet temperature) is measured.
operation
Measuring temperature range: -10ºC ~ 50ºC, Temperature unit: 1.0ºC
For the measuring sensor, select the indoor unit inlet or remote controller sensor in the setting of indoor units.
The output for changes will be output at the change exceeding a certain change range.
Even in the case of no change, the current value will be output after a certain time is elapsed.
The value of the changing range is set by the configuration property.
Communication Image
Renewal
The output for changes will be
output at the change exceeding a
certain change range.
Renewal
The current value will be output
after a certain time is elapsed.
Restrictions
- A difference of the display value of local remote control and BMS
With monitor timing, the display value of local remote control and BMS may change.
- Depending on the connecting number of indoor unit, the monitor interval that can be set is different.
To set a periodical monitor interval below 10 minutes, it is required to change SW1-3 on LM ADAPTER to ON. Please make the
connecting number 30 sets or less.
- The changing range: 0.5 ℃~2.0 ℃, Temperature unit: 0.5 ℃
Operated for 0.49℃ or less (except –0.01 ℃) --- Set to 0.5 ℃
Operated for –0.01℃ --- Set to 1.0 ℃
Operated for 2.01℃ or more --- Set to 2.0℃
BMS
state [xx℃]
Update interval(*1)
state [xx℃]
44
LM-AP
Space temp. demand
state [xx℃]
Space temp. demand
state [xx℃]
*1: Setting by Send Heartbeat_2【nciSndHrtBt_2】
LMAP03U
IC