Mitsubishi Electric LMAP03U Technical Manual page 67

Lm adapter for air conditioning network system
Hide thumbs Also See for LMAP03U:
Table of Contents

Advertisement

Function – [Effective Offline Mode]
Function
[Effective Offline Mode]
Description
Defines the offline mode setting when the LM ADAPTER power is turned ON.
Using CP
【nciOffline】
Control unit
LM ADAPTER
Relating CP
Nothing
Data holding
Memorizing set values in nonvolatile memory.
Reference NV
Nothing
Purpose
The mode will be fixed to judge whether the initialization is commenced at the powering of LM ADAPTER.
In the case when the OFF line mode is set in valid, the OFF line mode will forcibly be commenced for about 20
Outline of
minutes after powering LM ADAPTER. If Poll (Fetch) demand is presented to the input variable and outdoor
operation
variable during this time, the null will be responded.
After 20 minutes elapsed, ON line mode will be set.
Communication Image
Initialization setting of LM ADAPTER
20 minutes after powering
Cautions
- To conduct binding, be sure to make the OFF line mode invalid.
- The mode change under OFF line mode will be invalid.
- This function is only effective during the initialization (20 minutes after powering) of LM ADAPTER.
BMS
LM-AP
Power Recovery
NC no response
[Query Status]
state [offline]
Poll demand[IC_01]
state [null]
[Query Status]
state [online]
Poll demand[IC_01]
state [Run]
64
LMAP03U
IC_01