Downloading Configuration - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa tcp bridge
Table of Contents

Advertisement

1MRS756019
5.8.
Ethernet Adapter
SPA/TCP Bridge
Installation and Commissioning Manual
9600 bps
*
19200 bps
*
38400 bps
*
Receive Timeout
*
Receive Timeout defines how long SPA-ZC 402 waits for the slave's respond
before it considers the slave to be non-responding. The unit is milliseconds.
Retransmissions
*
Retransmissions defines how many times a message is resent after connection is
considered to be temporarily broken.
SPA-Timesynch
*
If enabled, SPA-ZC 402 sends time synchronization messages to the relay. If
SPA-ZC 402 is not connected to a SNTP server, time synchronization to the
slave should be disabled as well.
Time Zone Correction
*
Due to the SNTP time synchronization, a time offset must be added to the SPA
time synchronization message depending on the time zone. The value is in
minutes and ranges from -720 to 720. It is comparable to the Coordinated
Universal Time (UTC).

Downloading configuration

After you have built the object tree and done the communication configuration, you
can download the configuration to SPA-ZC 402:
1. Select the SPAZC40x_SPA Device object and right-click to select the CID
Export.
2. If you download configuration to SPA-ZC 402 the first time, change the IP
address from default address (192.168.2.10) to new IP address according to the
planned network structure.
When downloading the device's configuration, the device's current IP address must
be used as Target IP Address, see Fig. 5.8.-1. When using previously non-
configured SPA-ZC 402, default value (192.168.2.10) should be used.
When the new configuration to SPA-ZC 402 is downloaded, Communication
Engineering Tool (CET) checks if the basic IP addresses are changed. If a change is
detected, CET asks whether new addresses are taken into use. If the changes are not
accepted, SPA-ZC 402 uses the old IP address from the previous configuration. The
IP addresses can be verified with, for example, IP Query Tool. For more information
about IP Query Tool, refer to Section 8.3. IP Query.