higher than 0.75 inches of water column, the
system is too restrictive and the installation is
unacceptable.
Although vertical orientation of the exhaust system is
acceptable, certain extenuating circumstances could
affect the performance of the dryer:
Only the rigid metal duct work should be used.
Venting vertical through a roof may expose the
exhaust system to down drafts causing an increase
in vent restriction.
Running the exhaust system through an uninsulated
area may cause condensation and faster
accumulation of lint.
Compression or crimping of the exhaust system will
cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a
minimum of every 18 months with normal usage. The
more the dryer is used, the more often you should check
the exhaust system and vent hood for proper operation.
EXHAUST DIRECTION
All dryers shipped from the factory are set up for rear
exhausting. However, on electric dryers, exhausting can
be to the right or left side of the cabinet or the bottom
of the dryer. On gas dryers, exhausting can be to the
right side of the cabinet or the bottom of the dryer.
Directional exhausting can be accomplished by
installing Exhaust Kit, P/N 131456800, available
through your parts distributor. Follow the instructions
supplied with the kit.

EXHAUST DUCT LOCATING DIMENSIONS

SAME AS OTHER SIDE
5 7/8
13 ½
3 3/4"
GAS SUPPLY REQUIREMENTS
Replace copper connecting pipe that
is not plastic-coated. Stainless steel or plastic-
coated brass MUST be used.
1. Installation MUST conform with local codes, or in
the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.1 (latest edition)
2. The gas supply line should be of 1/2 inch (1.27 cm)
pipe.
3. If codes allow, flexible metal tubing may be used to
connect your dryer to the gas supply line. The tubing
MUST be constructed of stainless steel or plastic-
coated brass.
4. The gas supply line MUST have an individual shutoff
valve.
5. A 1/8 inch (0.32 cm) N.P.T. plugged tapping,
accessible for test gauge connection, MUST be
installed immediately upstream of the gas supply
connection to the dryer.
6. The dryer MUST be disconnected from the gas supply
piping system during any pressure testing of the gas
supply piping system at test pressures in excess of
1/2 psig (3.45 kPa).
7. The dryer MUST be isolated from the gas supply
piping system during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig (3.45 kPa).

LOCATION OF YOUR DRYER

DO NOT INSTALL YOUR DRYER:

1. In an area exposed to dripping water or outside
weather conditions.
2. In an area where it will come in contact with curtains,
drapes, or anything that will obstruct the flow of
combustion and ventilation air.
3. On carpet. Floor MUST be solid with a maximum
slope of 1 inch (2.54 cm).
INSTALLATION IN RECESS OR CLOSET
4 3/8"
1. A dryer installed in a bedroom, bathroom, recess or
closet, MUST be exhausted outdoors.
3 3/4"
2. No other fuel burning appliance shall be installed in
the same closet as the Gas dryer.
3. Your dryer needs the space around it for proper
ventilation.
DO NOT INSTALL YOUR DRYER IN A CLOSET
WITH A SOLID DOOR.