Dimensions; Wiring And Installation - Honeywell IAQPoint2 Technical Manual

Indoor air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Dimensions

3.0 in.
(77 mm)
6.4 in.
(163 mm)
Figure 8. Monitors' sizes

Wiring and installation

IAQPoint2 models are available for wall-mounting or duct-mounting� Wall-mount
units can be installed on standard single-gang junction boxes� Locate the monitor
in an area easily accessible by a technician� Avoid locations in which the monitor
will be subjected to vibration or rapid temperature fluctuations� Follow local
regulations and site requirements� Position wall-mounted monitors at least 10 feet
(3 meters) from any air intakes or outlets� Install duct-mounted monitors in return-
air ducts (not in supply-air ducts)�
IAQPoint2 analog models are configured to source current only�
The monitor is supplied as part of an installation kit containing:
• IAQPoint2 monitor
• backplate
• two plastic anchors w/screws
• 5/32 inch Allen wrench
• Quick Start Guide (one page, paper)
An optional calibration kit is also available� The kit contains:
• test gas
• M-502875: 0�5LPM Regulator for 58 & 103L Cylinders
• M-502877: 0�5LPM Regulator for 17L Cylinders
• M-501038: CAL GAS 17L CYLINDER NITROGEN (N2)
• M-501011: CAL GAS 103L CYLINDER NITROGEN (N2)
• M-501010: CAL GAS 103L CYLINDER 1,000 PPM CO2 BAL N2
• M-500989: CAL GAS 103L CYLINDER 2,000 PPM CO2 BAL N2
• M-512438: CALIBRATION ADAPTER IAQPOINT
• M-508808: CAL KIT TUBING 6 FEET 1/8 I�D� X 1/4 O�D�
1 Wiring labels are of EIA485 standard�
1.5 in.
(38 mm)
3.0 in.
(77 mm)
8.7 in.
(222 mm)
IAQPoint2
1.3 in.
(33 mm)
3.0 in.
(77 mm)
4.6 in.
(118 mm)
1
4.6 in.
(118 mm)
11