Modbus Registers
Summary
CO
sensor good
This is true if the CO
2
VOC sensor good
This is true if the VOC sensor is fitted and has no faults.
Heartbeat
This bit alternate between true and false every 10 seconds�
Gas Conc low
This bit is true if the gas reading is less than the setpoint�
Temp sensor good This bit is true if the temperature sensor is fitted and reading correctly.
Reserved for future enhancements�
Reserved for future enhancements�
Reserved for future enhancements�
Humidity sensor
This bit is true if the humidity sensor is fitted and reading correctly.
good
Reserved for future enhancements�
Reserved for future enhancements�
Reserved for future enhancements�
Occupied Timer
This bit is true if the occupied timer inside the IAQPoint2 is running� See
Running
Figure 22 for an illustration of this�
Relay Fitted
This is true if the PEM backplate contains the optional relay�
Relay Energized
This bit is true if the relay is energized�
Reserved for future enhancements�
This reports gas concentration� If the CO
Gas displayed
in ppm from 0 to 5000. If the VOC sensor is fitted this will report the air
reading�
quality index from 0 to 100� If the gas sensor is faulty this will report
32767�
This reports temperature in tenths of a degree Celcius� (For example,
Temperature C
the temperature of a human body would be reported as 370�) If the tem-
observed
perature sensor is faulty or absent this will contain -2730�
rH reading, Ob-
This reports the relative humidity in percent from 0 to 100� If the humidity
served
sensor is faulty or absent this will contain -1�
This contains the gas setpoint� The scaling is the same as register
CO
/VOC setpoint
2
40102� It is not writable�
Temperature C
This contains the temperature setpoint� The scaling is the same as regis-
Setpoint
ter 40103� It is not writable�
rH setpoint
This contains the relative humidity setpoint� It is not writable�
This counts forever up from 1 to 10000 and then repeats� Some Modbus
Heartbeat
masters may need this to confirm the communication is working.
Reserved for future enhancements�
Reserved for future enhancements�
Writing a 1 to this will cause the "Occupied" icon to appear on the LCD�
Write Occupied
Writing anything other than 0 or 1 is illegal� See Figure 22 for an illustra-
tion of this�
Writing a 1 or 0 to this will activate the relay if the correctly configured.
Write Relay
Writing anything other than 0 or 1 is illegal� See Figure 22 for an illustra-
tion of this�