Honeywell IAQPoint2 Technical Manual page 39

Indoor air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

Calibrate > Cal Temperature
Cal Temperature
Current 77.3
Target
77.3 F
Calibrate Offset
Revert to Factory Cal
This screen is available only on models with the optional temperature humidity
sensor and after the level 2 password has been entered� This feature allows the
monitor to be installed in an area that is known to be characteristically cooler or
warmer than the rest of the space (e�g�, near a photocopier)� This requires that a
desired value ("target temperature") be entered�
The monitor is precalibrated so calibration is unnecessary�
Press the "Target" button to enter the target temperature through the numeric
keyboard, within a range from 32 to 122°F (0 to 50°C)� The default value is 68°F
ü
(20°C)� Press [
] to return to the Cal Temperature menu, then press the "Calibrate
Offset" button� The monitor will then calculate the difference between the room
temperature and the desired temperature� This difference is the offset� When the
calibration has been completed, "Calibration Done" will be displayed� Press [X] to
return to the Cal Temperature screen�
Calibrate > Cal rH
Calibrate RH
Current 44 %
Target 44 %
Calibrate Offset
Revert to Factory Cal
This screen is available only on models with the optional temperature humidity
sensor and only after the level-2 password has been entered� The monitor is
precalibrated so calibration is not necessary�
Curent value unit displays the current relative humidity�
The target relative humidity can be entered through the numeric keyboard within
a range from 0 to 100%� The default value is 45%� Calibrate offset allows the
monitor to be installed in an area that is known to be characteristically more or less
humid than the rest of the space, much like the temperature offset described in the
previous section�