IAQPoint2
Property
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service
units
object_identifier
object_type
event_state
object_name
out_of_service
present_value
reliability
status_flags
in_alarm
fault
overridden
out_of_service
units
62
BACNet Objects and Properties
Data Type
R
C
analog_value (3)
enumerated
R
C
analog_value (2)
enumerated
R
R
normal (0)
character string
R
N
"GAS_SPT_AV"
boolean
R
R
FALSE
"Gas threshold if CO2 fitted, 850 if VOC fitted, 50 (Copy of
real
R
N
setpoint on UI)"
enumerated
O
C
no_fault_detected (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
enumerated
R
C
"if CO2 fitted, ppm (96) if VOC fitted, % (98)"
R
C
analog_value (4)
enumerated
R
C
analog_value (2)
enumerated
R
C
normal (0)
character string
R
N
"TEMP_SPT_AV"
boolean
R
C
FALSE
real
R
N
"20 C Copy of setpoint on UI)"
enumerated
O
C
no_fault_detected (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
enumerated
R
N
"Celcisus (62) (Units here independent of UI and AI1)"
R
C
analog_value (5)
enumerated
R
C
analog_value (2)
enumerated
R
C
normal (0)
character string
R
N
"RH_SPT_AV"
boolean
R
C
FALSE
real
R
N
"50 % rH (Copy of setpoint on UI)"
enumerated
O
C
no_fault_detected (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
boolean
R
C
always false (0)
enumerated
R
C
percent_relative_humidity (29)
Read Value
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
"If CO2 fitted, 400 to 5000
if VOC fitted, 10 to 100"
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
"if Celcius, 10 to 35 if Fahrenheit 50
to 95"
not writable
not writable
not writable
not writable
not writable
"Fahrenheit (64) or Celcisus (62)"
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
0 to 100%
not writable
not writable
not writable
not writable
not writable
not writable
Writable Values