BACnet Protocol Implementation Conformance Statement
Analog Input Object
Optional Properties
Reliability
Present Value
– Range Restriction for GAS_RDG_AI (Object Identifier 0): 400 to 5000 ppm or
10 to 100% depending on sensor fitted�
– Range Restriction for TEMP_AI (Object Identifier 1): 10 to 35 degC or 50 to 95
degF
– Range Restriction for RH_AI (Object Identifier 2): 0 to 100%
Object Name
– Range restriction of 1-22 characters�
Engineering Units
– Only writable for TEMP_AI (Object Identifier 2)�
– Valid Options: Degrees C (62) or Degrees F (64)�
Note:
1- For conveying the absence of sensor in PEM SKUs "Reliability" property with
NO SENSOR value shall be used� The "status flags" property should convey
FAULT in this condition�
2- During the sensor fault conditions in PEM, the "Reliability" property with
UNRELIABLE_OTHER value shall be used� The "status flags" property should
convey FAULT in this condition�
Analog Value Object
Optional Properties
Reliability
Present Value
– Range Restriction for GAS_SPT_AV (Object Identifier 3): 400 to 5000 ppm or 10 to
100% depending on sensor fitted�
– Range Restriction for TEMP_AV (Object Identifier 4): 10 to 35 degC or 50 to 95
degF
– Range Restriction for RH_AV (Object Identifier 5): 0 to 100%
Object Name
– Range restriction of 1-22 characters�
56
Writable Properties (Not
must by the Standard)
Present Value
Out Of Service
Object Name
Engineering Units*
Writable Properties (Not
must by the Standard)
Present Value
Object Name
Engineering Units
Proprietary Property
None
Proprietary Property
None