IAQPoint2
Property
object_identifier
object_type
vendor_identifier
apdu_timeout
application_software_
version
description
firmware_revision
location
max_apdu_length_ac-
cepted
max_info_frames
max_master
model_name
number_of_apdu_retries
object_name
protocol_object_types_
supported
protocol_services_sup-
ported
protocol_version
segmentation_supported
system_status
vendor_name
protocol_revision
database_revision
60
BACNet Objects and Properties
Data Type
unsigned
R
N
1
enumerated
R
C
device (8)
enumerated
R
C
Honeywell Inc� (17)
unsigned
R
C
0
character string
R
C
v1
character string
O
C
Honeywell Indoor Air Quality Sensor
character string
R
C
v1
character string
O
N
"location"
unsigned
R
C
480
unsigned
O
C
1
unsigned
O
N
127
character string
R
C
IAQPoint2
unsigned
R
C
0
""IAQPoint2_" +
character string
R
C
lower 12 bytes of serial number"
"analog_input,
analog_value,
bit string
R
C
binary_input,
binary_output,
device"
"readProperty,
readPropertyMultiple,
bit string
R
C
writeProperty,
who_Has,
who_Is,"
unsigned
R
C
1
enumerated
R
C
no_segmentation (3)
enumerated
R
C
operational_read_only (1)
character string
R
C
Honeywell
unsigned
R
C
7
unsigned
N
C
default 0 - will increment on changes of object names
Read Value
0 to 4,194,302
not writable
not writable
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
not writable
1 to 127
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
Writable Values