Bacnet Objects And Properties - Honeywell IAQPoint2 Technical Manual

Indoor air quality monitor
Hide thumbs Also See for IAQPoint2:
Table of Contents

Advertisement

IAQPoint2
Property
object_identifier
object_type
vendor_identifier
apdu_timeout
application_software_
version
description
firmware_revision
location
max_apdu_length_ac-
cepted
max_info_frames
max_master
model_name
number_of_apdu_retries
object_name
protocol_object_types_
supported
protocol_services_sup-
ported
protocol_version
segmentation_supported
system_status
vendor_name
protocol_revision
database_revision
60

BACNet Objects and Properties

Data Type
unsigned
R
N
1
enumerated
R
C
device (8)
enumerated
R
C
Honeywell Inc� (17)
unsigned
R
C
0
character string
R
C
v1
character string
O
C
Honeywell Indoor Air Quality Sensor
character string
R
C
v1
character string
O
N
"location"
unsigned
R
C
480
unsigned
O
C
1
unsigned
O
N
127
character string
R
C
IAQPoint2
unsigned
R
C
0
""IAQPoint2_" +
character string
R
C
lower 12 bytes of serial number"
"analog_input,
analog_value,
bit string
R
C
binary_input,
binary_output,
device"
"readProperty,
readPropertyMultiple,
bit string
R
C
writeProperty,
who_Has,
who_Is,"
unsigned
R
C
1
enumerated
R
C
no_segmentation (3)
enumerated
R
C
operational_read_only (1)
character string
R
C
Honeywell
unsigned
R
C
7
unsigned
N
C
default 0 - will increment on changes of object names
Read Value
0 to 4,194,302
not writable
not writable
not writable
not writable
not writable
not writable
Any unique string 1-22 bytes
not writable
not writable
1 to 127
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
not writable
Writable Values

Advertisement

Table of Contents
loading

Table of Contents