Operation

First power-up

No calibration of the CO
immediately begin operation with the default parameters discussed in the Menus
section� If desired, the monitor can be calibrated, however� Calibration procedures
are described beginning on page 40�
NOTE
!
Expect some slight variability in the monitor's output when
initially powered up� The sensors will fully stabilize after two to
three weeks�

Commissioning

CO
Configurations
2
With Automatic Baseline Correction (ABC) enabled
When the monitor is first powered up with ABC enabled (the default is ABC on),
no calibration is required� ABC monitors the background CO
adjustments to the baseline calibration once every 24 hours� Within three weeks,
the CO
sensor will adjust to the environment and be performing at the specified
2
accuracy� No further adjustment or calibration of the CO
With ABC disabled
This section applies to display models only� For applications in which ABC is
disabled, the monitor must be calibrated at least annually to accommodate any
drift due to the environment in which it is installed and to compensate for the
sensor electronics�
When the monitor is first powered up with ABC disabled, allow it to operate for 24
hours in the environment in which it will be used� If necessary, check the accuracy
of the sensor by applying a known concentration of test gas, following the
instructions in this manual for proper calibration procedures�
Temperature and relative humidity
The monitor's internal temperature will stabilize about twenty minutes after first
being powered up� The monitor provides the capability to calibrate temperature
and humidity sensor readings� If, after the system has stabilized, it is determined
that a temperature offset is required, follow the instructions in this manual for
proper calibration procedures�
VOC Configurations
The VOC sensor used with the IAQPoint2 monitor requires no calibration but allow
it fifteen minutes to warm up each time power is applied� The sensor will use the
air in which it is powered up as the baseline� The VOC sensor will adapt to the
environment in which it is installed�
20
or VOC sensors is required at startup� The monitor will
2
levels and makes
2
sensor is required�
2