Honeywell OMNI 624 Installation And Setup Manual page 64

Fbii security system
Hide thumbs Also See for OMNI 624:
Table of Contents

Advertisement

OMNI624 Installation and Setup Guide
QUESTION 16 DISPLAY OPTIONS
This question defines display options. Enter the digits as follows:
Q 16, L1 – Enter the L1 digit from the table below.
L1
Armed Bypass
Entry
Display
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Q 16, L2 – Enter the L2 digit from the table below.
No
Daylight
Code
Saving
L2
Set
(Summer)
Entry
Time
Time
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
6–26
Display Fault
No AC Loss
On Entry
Display
Keyfob
Low
Keypad
Bat.
Extinguish
Display
Manual
Armed Bypass Display: If
Bypass Limit 3
selected, pressing the [BYPASS]
key will scroll bypassed zones
while the system is armed.
Display Fault on Entry: Display
faults (open zones) during entry
delay time.
No AC Loss Display: If selected,
the AC loss message will not be
displayed on LCD keypads.
Manual Bypass Limit 3: If
selected, no more than 3 zones can
be manually bypassed.
U L
No Code Set Time: If selected, allows Quick
Command #3 to set time. Intended for low-security
installations.
Daylight Saving (Summer) Time: If selected,
the system will automatically adjust for daylight
saving (summer) time (U.S. standard: First
Sunday in April at 2:00 AM, the clock goes ahead 1
hour; last Sunday in October at 2:00 AM, the clock
goes back 1 hour to standard time).
Keypad Extinguish: If selected, the keypad
display and LEDs will turn off after 1 minute of no
key presses.
Keyfob Low-Battery Display: This option
determines whether low-battery messages from
keyfobs will be displayed. If selected, display is
enabled. Note that even if this display is disabled,
keyfob low-battery conditions can be checked by
using the #56 Quick Command.
L1
L2
L3
Do not enable No AC Loss
Display (must display AC
loss) for UL installations.
L4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents