Q 13, L3 – Enter the L3 digit from the table below.
Pager Attempts
L3
Entry
1
2
3
0
disabled
✔
1
✔
2
✔
3
disabled
4
✔
5
✔
6
✔
7
8
disabled
✔
9
✔
A
✔
B
C
disabled
✔
D
✔
E
✔
F
Q 13, L4 – Enter the L4 digit from the table below.
Swinger
Count
L4
Bat
1
2
3
Entry
Test
0
Disabled
✔
1
✔
2
✔
3
✔
4
Disabled
✔
✔
5
✔
✔
6
✔
✔
7
8
Disabled
✔
9
✔
A
✔
B
✔
C
Disabled
✔
✔
D
✔
✔
E
✔
✔
F
Supervision
Time (Hours)
20M/
1*
6
18
24
✔
Pager attempts: This sets the number of times the
✔
system will send a report to a pager.
✔
✔
Supervision Time: This sets the maximum time
✔
interval within which the RF Receiver must hear from
✔
transmitters, otherwise an RF trouble report will be
✔
sent. 24 hours is recommended for 5800 and ZR500 RF
✔
devices.
✔
*When the 20M/1 selection is selected, the RF Receiver
must hear from the transmitters every 20 minutes when
✔
the system is disarmed and every hour when the system
✔
is armed.
✔
✔
✔
✔
✔
Delay
if Stay
Swinger Count: Sets the maximum number of messages (controlled
zone alarms or troubles) sent during an armed period.
Battery Test: If enabled, the system battery is tested for a period of 4
seconds per minute. When not enabled, the battery is tested for 1
second per minute.
Delay if Stay: If enabled, the dial delay set for a controlled zone will
✔
only be applicable when the system is armed stay. When the system is
✔
armed in any other mode, the zone dial delay will not be applicable.
✔
This option does not affect 24-hour type zones.
✔
✔
✔
✔
✔
Section 6. System Programming