Frequency Reference by Pulse Train Input

Frequency reference can be set by pulse train input from the control cir-
cuit terminals.
• Input pulse specifications
• Low-level voltage: 0.8 V or less
• High-level voltage: 3.5 to 32 V
• H duty: 30 % to 70 %
• Pulse frequency: 0 to 33 kHz
• Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of
the maximum input pulse frequency and actual input pulse fre-
quency by the maximum output frequency.
Reference
frequency
FWD Run/Stop
REV Run/Stop
Pulse
Reference
Device
Constant
No.
n003
Run Command Selection
n004
Frequency Reference
Selection
n149
Pulse Train Input Scaling
122
Input pulse frequency
=
Maximum pulse train frequency (n149) x 10
S1
SC
RP
Name
IM
Run/stop and FWD/REV run can be
selected by a switch connected
to the multi-function input.
[Set S1 and S2 to FWD run/stop
(n050 = 1) or REV run/stop (n051 = 2).]
Set the frequency by a pulse train
input signal [0 % to 100 %
(maximum frequency)/0 to 33 kHz]
from the control circuit terminal.
Unit
Setting
Range
-
0 to 3
-
0 to 9
1=10
100 to 3300
Hz
(33 kHz)
Maximum output
x
frequency (n011)
Factory
Setting
0
1
2500
(25 kHz)