Daikin RZQG71~140L7V1B Service Manual page 115

Skyair gqi-eco series heat pump r-410a 50hz
Table of Contents

Advertisement

Function Details
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
T = Indoor suction air temperature – temperature set by remote controller (Cooling)
T = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
T > +0.5°C
Thermostat OFF Condition
104
• ∆T ≤ – 0.5°C continues for 1 minute (for RZQG71L)
• ∆T ≤ – 0.5°C continues for 1 minute
or
• 5 minutes or more after start up
•&
(for RZQG100 - 140L)
• ∆T ≤ – 2°C (Cooling)
• ∆T ≤ – 2.5°C (Heating)
When changed suddenly from ∆T ≥ +1.5°C to ∆T ≥ -0.5°C
ESIE12-06
Function and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents