Daikin RZQG71~140L7V1B Service Manual page 147

Skyair gqi-eco series heat pump r-410a 50hz
Table of Contents

Advertisement

Field Setting from Remote Controller
2.5.2 External Activation from Optional PCB
Graph
Quiet (low noise) operation can also be activated from the optional PCB.
Quiet (low noise) operation will start when the contact on LNOP-COM is closed and will remain
active as long as the contact is closed. No field setting on the outdoor unit or by remote
controller is required.
Quiet (low noise) operation will be ended when the contact is re-opened.
Use of the KRP58M enables the use of an external time clock.
Capacity priority
Same as with the automatic control, priority for capacity can be set. Prioirity for capacity will be
activated by changing field setting 26-0-03 in combination with the closed contact on KRP58M.
Setting
Description
Quiet (low noise)
operation
Exceptions
The Quiet (low noise) operation will be overruled in the following conditions:
 Pump down residual operation
 Startup control
 Defrost operation
 Oil recovery
Sound reduction
Sound reduction
136
Power supply connector
(on outdoor PCB X77A)
Output on X801M = 12VDC, 12mA
Maximum wire length = 100 meter
Mode
No.
16(26)
Model
RZQG71
DS1
ON
OFF
1 2 3 4
X800M
X801M
3
2
1 LNOP COM
Second Code No.
First
Code
No.
01
0
Factory
setting
RZQG100
6 dBA
5 dBA
ESIE12-06
Transmission connector
(on outdoor PCB X6A)
X801M
3
2
1 LNOP
COM
02
03
Capacity
priority
setting
RZQG125
RZQG140
6 dBA
7 dBA
Field Setting
04