Daikin RZQG71~140L7V1B Service Manual page 142

Skyair gqi-eco series heat pump r-410a 50hz
Table of Contents

Advertisement

ESIE12-06
Airflow Rate
Set the airflow when thermostat OFF by the combination of "Fan OFF at Thermostat OFF"
11(21)-2," Fan speed heating thermostat OFF" 12(22)-3 and "Fan speed cooling thermostat
OFF" 12(22)-6.
A : 6 minutes OFF / 1 minute LL
B : 6 minutes OFF / 1 minute setting airflow
C : 6 minutes OFF / 1 minute L
Set the airflow by the combination of 3 modes as below.
Airflow Rate Setting during Heating (FCQG Only)
For the purpose of securing airflow range during heating, the number of revolutions of fan during
heating can be changed. Make the setting according to installation environment.
Field Setting
Mode No.
First Code No.
11(21)
2
12(22)
3
12(22)
6
When thermostat
Cooling
OFF
When thermostat
Dry
OFF
When thermostat
OFF
Heating
When defrost hot
start
Mode No.
First Code No.
11 (21)
Factory
setting
01
01
01
01
01
02
02
01
01
Setting
LL
LL
C
C
C
LL
LL
Setting
OFF
OFF
OFF
01
3
Standard
Field Setting from Remote Controller
Second Code No.
Field setting
01
02
02
02
01
01
02
01
02
Setting
A
B
C
C
C
Setting
A
A
Setting
OFF
OFF
OFF
Second Code No.
02
Slightly up
02
02
02
02
01
02
A
B
C
C
Setting
OFF
OFF
03
Up
131