Settings Contents and Code No. for Indoor Units

First
Mode
Code
No.
No.
0
Filter cleaning sign interval Long life filter
10 (20)
2
Remote controller thermistor
3
Filter cleaning sign
2
Fan OFF at Thermostat OFF
11 (21)
3
Airflow rate setting during heating
4
Automatic operation mode control
3
Fan speed heating thermostat OFF
12 (22)
5
Automatic restart after power failure reset
6
Fan speed cooling thermostat OFF
High air outlet velocity (for high ceiling
0
applications)
13 (23)
1
Selection of airflow direction
4 (2)
Airflow range setting
15 (25)
5
Individual setting of ventilation
Note:
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. For FHQG, the second code No. of the "Airflow range setting is set at "03".
3. "88" may be displayed to indicate the remote controller is resetting when returning to the
2.3.1 Detailed Explanation of Setting Modes
Filter Cleaning Sign Interval
When "Display" is selected in "Filter cleaning sign" after the unit runs for certain time, "Filter
cleaning" will be displayed on the remote controller. This setting is used when the display
interval of "Filter cleaning" needs to be changed on occasions such as when the filter has been
heavily contaminated.
Mode No.
Remote Controller Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "02" and room temperature is controlled by the
indoor unit suction air thermistor.
When the Second Code No. is set to "01", room temperature is controlled by the indoor unit
suction air thermistor and the room temperature thermistor in remote controller as following
figures.
Field Setting
Description of Setting
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses. (Even if the
setting are made for the entire group, the display always indicates "01".)
normal mode.
First Code
Second
No.
Code No.
10 (20)
0
First Code
Mode No.
No.
10 (20)
2
01
2,500 hrs.
Enabled
Display
Normal
Standard
Available
LL-speed
Disabled
LL-speed
Standard
4-way flow
Upper
Normal
Long Life Filter
01
2,500 hrs.
02
1,250 hrs.
Second
Thermistor that controls room temperature
Code No.
Room temperature thermistor in remote controller and
01
indoor unit suction air thermistor
02
Indoor unit suction thermistor
Field Setting from Remote Controller
Second Code No.
02
03
1,250 hrs.
Disabled
No display
OFF
Slightly up
Up
Prohibition
Set-speed
Enabled
Set-speed
Slightly up
Up
3-way flow
Normal
Lower
Individual
operation
Setting
Contamination Light
Contamination Heavy
04
129