3.2.19 Low Outdoor Air Temperature Control in Cooling Operation
Controls compressor and outdoor unit fan under low outdoor air temperature condition to secure
pressure difference between high and low pressure.
Hp: High pressure
Lp: Low pressure
Ta: Outdoor air temperature
Tfin: Inverter fin temperature
OR
&
Hp < 1.86MPa
Ta < 25°C
OR
&
Hp < 1.57MPa
OR
&
Hp < 1.57MPa
Tfin < 66°C
Frequency Restriction
112
Hp-Lp < 0.93MPa
Compression ratio < 2.1
Compressor operation frequency
restriction (refer to the followings)
Hp-Lp < 0.78MPa
Compression ratio < 1.8
Outdoor unit fan
-1 step/90 sec.
Hp-Lp < 0.78MPa
Compression ratio < 1.8
No frequency
restriction
Normal operation
Outdoor unit fan: Stop
RZQG71L
Lower limit frequency
Ta
25°C
Step 11
Upper limit frequency
Ta > 27°C
Step 17
Hp-Lp > 1.08MPa
OR
Hp < 2.94MPa
Compression ratio > 2.4
OR
Ta > 27°C
Outdoor unit fan
+1 step/90 sec.
Hp-Lp > 0.98MPa
&
Compression ratio > 2.2
OR
Hp > 2.25MPa
Outdoor unit fan
Step 1
Hp-Lp > 0.88MPa
&
Compression ratio > 2.0
OR
Hp > 1.66MPa
Tfin ³ 81°C
RZQG100-140L
Lower limit frequency
Step 9
Upper limit frequency
Step 15
Function and Control