ESIE12-06
4.3

Safety Devices

4.3.1 Outdoor Unit
Model
RZQG71L
RZQG100L
RZQG125L
RZQG160L
4.3.2 Indoor Unit
Model
FCQG
FHQG
Service Diagnosis
High pressure switch
Open
4.0 MPa +0/– 0.15
Thermal protector
Abnormal
Close
3.0 MPa ± 0.15
Reset (automatic)
Troubleshooting by Remote Controller
Fuse
6.3A/250V (F1U), 3.15A/250V (F6U)
6.3A/250V (F1U, F2U, F3U),
5A/250V (F6U)
Fuse
N.A.
3.15A/250V (F1U)