4.19 High Pressure Switch System Abnormality

H3
Remote
Controller
Display
Applicable
RZQG125, 140
Models
Method of Error
The protection device circuit checks continuity in the high pressure switch (S1PH).
Detection
Error Decision
When there is no continuity in the high pressure switch during compressor stops operating.
Conditions
Supposed
 Incomplete high pressure switch
Causes
 Defective connection of high pressure switch connector
 Defective outdoor unit PCB
 Disconnected lead wire
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is protection
high pressure switch connector
(∗1) correctly connected to
outdoor unit PCB?
YES
Wait for 10 minutes after the unit
stops operating, then check the
following.
Is there continuity
in each protection high
pressure switch?
YES
Is there continuity
in lead wire?
YES
Note:
1 Connector and indoor unit PCB
Model
Connector for high pressure switch
RZQG
Service Diagnosis
NO
NO
NO
X32A
Troubleshooting by Remote Controller
Connect correctly.
Replace the high pressure
switch with no continuity.
Resistance in normal operation :
10Ω or less
Replace the lead wire.
Replace the outdoor unit PCB
(A1P).
PCB
A1P
209