LED status
Inverters (FR-A8NC)
Master
unit
Station 1
Station 2
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
RUN
RUN
TIME
L.RUN
L.RUN
LINE
SD
SD
or
RD
RD
TIME
L.ERR
L.ERR
LINE
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
: On, : Off, : Flicker, : Any of on, flicker or off
94
HOW TO CHECK FOR ERROR USING THE LEDS
Station 3
RUN
Since the L.ERR LED of the FR-A8NC on
L.RUN
station 2 is on, the FR-A8NC itself on station 2
SD
is affected by noise.
RD
(L.RUN may go off.)
L.ERR
RUN
Since the L.ERR LEDs of the FR-A8NC on
L.RUN
station 2 and later are on, the transmission
SD
cable between the inverters of stations 2 and 3
RD
is affected by noise. (L.RUN may go off.)
L.ERR
RUN
The terminating resistor has been left unfitted,
L.RUN
or the one-touch connector plug with
SD
terminating resistor has been left unfitted.
RD
(L.RUN may go off.)
L.ERR
Cause
Securely earth (ground) each
inverter and the master module.
Check if shielding (drain) wires of
the CC-Link dedicated cable are
properly inserted to the one-touch
communication connector plug.
(Refer to
Also run it as far away as
possible from the power lines.
(100 mm or more)
• Check that the setting of the
• Use the one-touch connector
Corrective action
page
16)
terminating resistor selection
switch is correct.
(Refer to
page
23)
plug with terminating resistor.
(Refer to
page
20)