About setting
• Operation at an error occurrence
Error definition
0
1
Communication line
2
3
0, 3
Communication option
itself
1, 2
When the communication returns to normal within the time period set in Pr.500, the communication option error (E.OP1) does not occur.
• Operation after the time in Pr.500 elapses after an error occurrence
Error definition
0
1
Communication line
2
3
0, 3
Communication option
itself
1, 2
When an error occurs, the motor is decelerated or coasts to stop with the fault output independently of the Pr.500 setting.
32
INVERTER SETTING
Pr.502 setting
Operation
Continued
Coast to stop
Decelerated to stop
Pr.502 setting
Operation
Coast to stop
Decelerated to stop
Continues operation
with the Pr.779 setting.
Kept stopped
Indication
Normal indication
E. 1 lit
E. 1 lit after stop
Indication
E.OP1 lit
E.OP1 lit after stop
Normal indication
E.OP1 kept lit
Fault output
Not provided
Provided
Provided after stop
Fault output
Provided
Provided after stop
Not provided
Kept provided