Program Example For Parameter Writing - Mitsubishi Electric FR-A8NC Instruction Manual

Plug-in option cc-link communication function
Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

8.6

Program example for parameter writing

The following program changes the setting of Pr.7 Acceleration time of station 1 inverter to 3.0 s.
• Acceleration time writing instruction code: H87 (hexadecimal)
• Acceleration time set data: K30 (decimal)
For the parameter instruction codes, refer to the Instruction Manual (Detailed) of the inverter.
The reply code at the time of instruction code execution is set to D2. (Refer to
X0
X0F
X1
0
M0
X20
7
M300
11
M301
X100F
13
M302
X100F
22
28
NOTE
• For parameters having numbers 100 and later, change their link parameter extended settings (set them to other than
H00). Refer to the parameter list of the Instruction Manual (Detailed) of the inverter for settings.
• For other functions, refer to the instruction codes (Refer to
82
PROGRAMMING EXAMPLES
SW80.0
MOV H87 W102
MOV K30 W103
MOV W2
page
64)
Check the data link status of the station 1
M0
PLS M300
SET M301
Write Pr.7 write (H87) to RWw2 and
acceleration time setting data (K30) to RWw3.
SET Y100F
Turn on the instruction code execution request (RY0F)
RST M301
SET M302
Read reply code (RWr2) to D2 when the instruction
D2
code execution completion (RX0F) turns on.
Turn off the instruction code execution request (RY0F)
RST Y100F
RST M302
END