9.3
Communication stops during operation
• Check that the option unit (FR-A8NC) and CC-Link dedicated cables are fitted properly.
(Check for contact fault, break in the cable, etc.)
• Check that the programmable controller program is executed properly.
• Check that data communication has not stopped due to an instantaneous power failure, etc.
LED status
Inverters (FR-A8NC)
Master
unit
Station 1
Station 2
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
RUN
RUN
TIME
L.RUN
L.RUN
LINE
SD
SD
or
RD
RD
TIME
L.ERR
L.ERR
LINE
RUN
RUN
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
: On, : Off, : Flicker, : Any of on, flicker or off
Station 3
RUN
Since the L.RUN LEDs of the FR-A8NC on
L.RUN
station 1 and the FR-A8NC on station 3 are off,
SD
the station numbers of the inverters set as
RD
stations 1 and 3 are the same.
L.ERR
RUN
Since the L.RUN and SD LEDs of the FR-
L.RUN
A8NC on station 2 are off, the transmission
SD
speed setting of the FR-A8NC on station 2 is
RD
wrong within the setting range (0 to 4).
L.ERR
RUN
Since the L.ERR LED of the FR-A8NC on
L.RUN
station 3 flickers, the setting switch of the FR-
SD
A8NC on station 3 was moved during normal
RD
operation.
L.ERR
Cause
HOW TO CHECK FOR ERROR USING THE LEDS
Corrective action
After correcting the repeated
station numbers of the inverters
using Pr.542 Communication
station number (CC-Link),
switch power on again.
After correcting the transmission
speed setting using Pr.543 Baud
rate selection (CC-Link), switch
power on again.
After returning the setting switch
of the FR-A8NC to the original
position using Pr.542
Communication station
number (CC-Link) or Pr.543
Baud rate selection (CC-Link)
power on the inverter again.
93