Horizontal Termination Venting Con gurations
See venting accessories list on pages 40––41 for allowable components.
Rear Outlet w/Vertical Rise —Horizontal
Termination
•• 817VAK Vent Collar Adapter required;
•• Maximum 2 x 90° elbows allowed (or equivalent: 2 x 45°
elbows = 1 x 90° elbow);
•• A Terminal Guard such as 845TG is required where the vent
terminal is located within 7’' 0 ”" of grade or where accessible.
D: Vertical pipe run
E: Horizontal pipe run (Total
before and after elbows) E
+ E
2
F: Clearance to combustible
materials above horizontal
pipe run
G: Clearance to combustible
materials below horizontal
pipe run
H: Clearance to combustible
materials all round vertical
pipe run and at sides of hori-
zontal pipe run
Top Outlet w/Vertical Rise—Horizontal
Termination
See Conversion to Top Outlet for Solid Direct Vent Co-axial
Piping in Appliance Preparation section for conversion to
top outlet;
•• 817VAK Vent Collar Adapter required;
•• Maximum 2 x 90° elbows allowed (or equivalent: 2 x 45°
elbows = 1 x 90° elbow);
•• A Terminal Guard such as 845TG is required where the vent
terminal is located within 7’' 0 ”" of grade or where accessible.
D: Vertical pipe run (total)
E: Horizontal pipe run (Total)
F: Clearance to combustible
materials above horizontal
pipe run
G: Clearance to combustible
materials below horizontal
pipe run
H: Clearance to combustible
materials all round vertical
pipe run and at sides of hori-
zontal pipe run
Minimum Maximum
12”"
8’'
(30 cm)
(244 cm)
4’'-6”"
-
1
(137 cm)
2-5/8”"
-
(6.7 cm)
1-5/16”"
-
(3.3 cm)
1-5/16”"
-
(3.3 cm)
Minimum Maximum
9”"
8’'
(23 cm)
(244 cm)
4’'-6”"
-
(137 cm)
2-5/8”"
-
(6.7 cm)
1-5/16”"
-
(3.3 cm)
1-5/16”"
-
(3.3 cm)
530
engine
14" (36 cm) max
combustible wall
530
engine
QUALIFIED
INSTALLER
Use 845TG vent
guard with a
vent terminal
located at less
than 7' (2.13 m)
above grade
Approved
side wall
termination
Use 845TG vent
guard with a
vent terminal
located at less
than 7' (2.13 m)
above grade
Approved
through wall
shield/thimble
14" (36 cm)
max.
combustible
wall
21