Horizontal Termination Venting Con gurations
INSTALLER
See venting accessories list on pages 40––41 for allowable components.
Rear Outlet—No Vertical Rise
Flat on the Wall
•• Maximum 26”" horizontal pipe length;
•• 817VAK Vent Collar Adapter required if using other
than Valor’' s 551DVK pipe with termination;
•• A Terminal Guard such as 845TG is required where
the vent terminal is located within 7’'0”" of grade or
where accessible.
In Corner—No Vertical Rise
•• Maximum 1 x 45° elbow allowed;
•• Maximum 18”" horizontal pipe length;
•• A Terminal Guard such as 845TG is required where
the vent terminal is located within 7’'0”" of grade or
where accessible.
20
14" (36 cm) max.
within
combustible wall.
26" (66 cm) max.
vent length
530
Approved
engine
side wall
termination
Approved
trough wall
shield/thimble
Max. 26" (66 cm)
530
engine
Use 845TG vent
guard with a
vent terminal
located at less
than 7' (2.13 m)
above grade
18" (46 cm)
max vent pipe
Approved
side wall
termination
Approved
through wall
shield/thimble