kozy heat SLA-42 Installation And Operation Manual page 18

Direct vent linear fireplace
Table of Contents

Advertisement

MIN. / MAX. HORIZONTAL VENTING
TERMINATION CAP
HORIZONTAL VENT
HEAT SHIELD
90° ELBOW
HORIZONTAL RUN
VERTICAL RISE
Figure 17a
The horizontal vent heat shield included with this fireplace must be installed when incorporating minimum horizontal venting.
This applies to Nat. and LP minimum horizontal venting configurations.
IMPORTANT
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2" (114mm) - 6-1/2" (165mm) wall thickness), or
#800-WPT2 (6-1/2" (165mm) -12-1/2" (318mm) wall thickness) must be used on all horizontal vent runs.
Flame height and appearance will vary depending upon venting configuration and type of fuel used.
HORIZONTAL VENT HEAT SHIELD
1.
Loosen, but do not remove center two screws on top of fireplace.
2.
Bend horizontal heat shield at perforation to a 90° angle. Slide (2) slots on horizontal vent heat shield under loosened screws.
3.
Re-tighten screws.
ATTACHMENT SCREWS
Figure 17b
VENTING
NAT
MINIMUM: 12" (305mm) vertical rise / 9" (229mm) horizontal.
MAXIMUM: 12" (305mm) vertical rise / 12ft. (3.66m) horizontal.
LP
MINIMUM: 18" (457mm) vertical rise / 9" (229mm) horizontal .
MAXIMUM: 18" (457mm) vertical rise / Max. 12ft. (3.66m) horizontal.
.
17