Table Of Parameters - Carel ir33 Universale series User Manual

Universale electronic controller
Hide thumbs Also See for ir33 Universale series:
Table of Contents

Advertisement

Par.
Description
St1
Set point 1
St2
Set point 2
c0
Operating mode
1=direct
2=reverse
3=dead zone
4=PWM
5=alarm
6=direct/reverse from digital input1
7=direct: set point & diff erential from digital input 1
8=reverse: set point & diff erential from digital input 1
9=direct & reverse with seperate set points.
P1
Set point diff erential 1
P2
Set point diff erential 2
P3
Dead zone diff erential
c4
Authority.
Validity : mode 1 or 2
c5
Type control
0=ON/OFF (Proportional)
1=Proportional+Integral+Derivative (PID)
c6
Delay between activations of 2 diff erent relay outputs
Validity: c0≠ 4
c7
Minimum time between activations of same relay output
Validity: c0 ≠ 4
d1
Minimum time between deactivations of 2 diff . relay outputs
Validity: c0 ≠ 4
c8
Minimum relay output off time
Validity: c0 ≠ 4
c9
Minimum relay output on time
Validity: c0 ≠ 4
c10
Status of control outputs with probe alarm
0=All outputs OFF
1= All outputs ON
2="Direct" outputs on, "reverse" outputs off
3= "Reverse" outputs on, "direct" outputs off
c11
Output rotation
0=Rotation not active
1=Standard rotation (with 2 o 4 relays)
2=Rotation 2+2(compressors on relays 1 & 3)
3=Rotation 2+2 only for models with 4 outputs (Z & A)
4=Rotation of outputs 3 & 4, not 1 & 2
5=Rotation of outputs 1 & 2, not 3 & 4
6=Separate rotation of pairs 1,2 (with each other) & 3,4
7=Rotation of outputs 2,3,4, not output 1
Validity: c0=1,2,7,8 & c33=0
c12
PWM cycle time
c13
Type of probe
0=NTC standard range(-50T+90°C)
1=NTC enhanced range(-40T+150°C)
2=PTC standard range(-50T+150°C)
3=Pt1000 standard range(-50T+150°C)
P14
Calibration of probe 1
P15
Calibration of probe 2
c17
Probe disturbance fi lter
c18
Temperature unit of measure
0=°C
1=°F
c19
Operation of probe 2
0=not enabled
1=diff erential operation
2=compensation in cooling
3=compensation in heating
4=compensation always active
5=enable logic on absolute set point(*)
6= enable logic on diff erential set point(*)
Validity: c0 =1,2
c21
Minimum value of set point 1
c22
Maximum value of set point 1
c23
Minimum value of set point 2
c24
Maximum value of set point 2
P25
Low temperature alarm threshold
if P29=0, P25=0: threshold disabled
if P29=1, P25=-50: threshold disabled

7. TABLE OF PARAMETERS

Note Def
20
40
2
2
2
2
0.5
0
5
0
0
0
0
0
0
20
0
0
0
4
0
0
-50
60
-50
60
-50
37
Min
Max UoM Type CAREL SVP ModBus®
c21
c22
°C/°F A
3
c23
c24
°C/°F A
4
1
9
-
I
39
0.1
50
°C/°F A
5
0.1
50
°C/°F A
6
0
20
°C/°F A
7
-2
2
-
A
8
0
1
-
D
163
0
255
s
I
40
0
15
min
I
41
0
255
s
I
42
0
15
min
I
43
0
15
min
I
44
0
3
-
I
45
0
7
-
I
46
0.2
999
s
A
9
0
3
-
I
47
-20
20
°C/°F A
10
-20
20
°C/°F A
11
1
15
-
I
48
0
1
-
D
164
0
6
-
I
49
-50
c22
°C/°F A
14
c21
150
°C/°F A
15
-50
c24
°C/°F A
16
c23
150
°C/°F A
17
-50
P26
°C/°F A
18
ir33 universale +030220801 - rel. 1.0 - 16.04.2008
ENG
R/W
Icon
4
R/W
5
R/W
112
R/W
6
R/W
7
R/W
8
R/W
9
R/W
25
R/W
113
R/W
114
R/W
115
R/W
116
R/W
117
R/W
118
R/W
119
R/W
10
R/W
120
R/W
11
R/W
12
R/W
121
R/W
26
R/W
122
R/W
15
R/W
16
R/W
17
R/W
18
R/W
19
R/W